Rating:
Information pump assy, fuel fe Denso
Scheme #.#:
№
Qty
Part num
Name
Remarks
Manufacture num
Cross reference number
Part num
Firm num
Firm
Name
09210-00890
PUMP ASSY, FUEL FE
Information:
Table 1
PID Security Levels for EMCP II    
LEVEL NO.    PID    
0        
1     $00 $0D (R), $00 $40 (R), $00 $42 (R),
$00 $44 (R), $00 $54 (R), $00 $5E (R),
$00 $80 (R), $00 $82 (R), $00 $83 (R),
$00 $84 (R), $F0 $13 (R), $F0 $14 (R),
$F0 $2A (R), $F0 $8F (R), $F0 $B0 (RW),
$F0 $B1 (R), $F0 $B2 (R), $F0 $B3 (R),
$F0 $B4 (R), $F1 $D3 (R), $F1 $D4 (R),
$F1 $D5 (R), $F1 $D6 (R), $F2 $13 (R),
$F2 $CB (R), $F2 $CC (R), $F2 $D6 (R),
$F2 $D7 (R), $F4 $40 (R), $F4 $41 (R),
$F4 $42 (R), $F4 $43 (R), $F4 $44 (R),
$F4 $46 (R), $F4 $47 (R), $F4 $48 (R),
$F4 $49 (R), $F4 $FA (R), $F4 $4B (R),
$F4 $4C (R), $F4 $4D (R), $F4 $60 (R),
$F4 $61 (R), $F4 $62 (R), $F4 $63 (R),
$F4 $64 (R), $F4 $65 (R), $F4 $66 (R),
$F4 $67 (R), $F4 $68 (R), $F4 $69 (R),
$F4 $6A (R), $F4 $6B (R), $F4 $6C (R),
$F4 $6D (R), $F4 $C3 (R), $F4 $C4 (R),
$F4 $C7 (R), $F4 $C8 (R), $F4 $C9 (R),
$F4 $CA (R), $F4 $CB (R), $F4 $CF (R),
$F4 $D0 (R), $F4 $D1 (R), $F4 $D2 (R),
$F5 $0B (R), $F4 $0C (R), $F5 $0D (R),
$F5 $3E (R), $F5 $57 (R), $F8 $14 (R),
$FC $0D (R), $FC $0F (R), $FC $10 (R),
$FC $11 (R), $FC $12 (R), $FC $13 (R),
$FC $14 (R), $FC $14 (R), $FC $15 (R),
$FC $17 (R), $FC $18 (R), $FC $19 (R),
$FC $1A (R), $FC $1B (R), $FC $1C (R),
$FC $1D (R), $FC $1E (R), $FC $1F (R)    
2     $00 $0D (W), $00 $83 (W), $F0 $B1 (W),
$F0 $B2 (W), $F2 $13 (W), $F2 $CC (W),
$F4 $4D (W), $FC $0D (W), $FC $10 (W)    
3        Each Parameter Identifier (PID) has an identifier that is one or two bytes in length. The identifier is hexadecimal. The PID is followed by one or more data bytes. For example, the Relay Control PID is $F4 $4C. This PID is followed by two bytes of data (aa) that contain the status of the Generator Set Status Control relays. Data bits are given as binary digits unless the number is preceded by $. All data is sent with the most significant byte first.The following chart is a quick reference list of the Parameter Identifiers (PID).
Table 2
Parameter Identifier Reference Chart for EMCP II Applications    
PID    Description    
$00 $0D
a     Remote Fault Reset
Used to read the status of or reset inactive shutdown and alarm faults on the GSC.    
$00 $40
aa     Generator Set Engine RPM
Used to read the generator set engine rpm.    
$00 $42
aa     Generator Set Ring Gear Teeth Setpoint
Used to read the number of ring gear teeth the GSC uses to calculate engine speed.    
$00 $44
aa     Engine Coolant Temperature (°C)
Used to read the temperature of the engine coolant.    
$00 $54
aa     Engine Oil Pressure kPa
Used to read the oil pressure of the engine in kPa.    
$00